Authors: | Nilges, Matthias Mackow, Andrzej Kizilcay, Mustafa |
Editors: | Kubis, Andreas Rehtanz, Christian Shapovalov, Anton Hilbrich, Dominik Plota, Ewa |
Title: | Blitzeinschlagsanalyse für rückwärtige Überschläge einer Hybridleitung |
Language (ISO): | de |
Abstract: | A new method to transfer energy over short and long distances is to use hybrid lines. In this paper a lightning surge analysis for backflashovers on overhead transmission lines with one DC and three AC systems on the same tower is considered. Lightning strikes are the most common source of failures on transmission systems and are not considered for hybrid lines. The main aim is to get essential information about the behavior of the HVDC system due to a backflashover. We simulate a lightning stroke into a hybrid line using EMTP-ATP. The results clearly show that the 110-kV AC systems provide protective effects for the HVDC system. Therefore, it is concluded that the backflashover performance of HVDC systems is better on AC/DC hybrid lines, compared to identically constructed towers with just one HVDC system installed. |
Subject Headings: | backflashover EMTP-ATP transmission tower model hybrid line lightning surge analysis |
URI: | http://hdl.handle.net/2003/33980 http://dx.doi.org/10.17877/DE290R-7397 |
Issue Date: | 2015-01-14 |
Is part of: | Power and Energy Student Summit(PESS) 2015, January 13th-14th, Dortmund Germany |
Appears in Collections: | Power and Energy Student Summit (PESS) 2015 |
This item is protected by original copyright |
This item is protected by original copyright rightsstatements.org